• Basic data
    • SeriesS20
  • Functions
  • Characteristic parameters
    • Mission time20 years, EN ISO 13849-1
    • B10d2,000,000 number of cycles
  • Electrical data
    • Usage category at DC 13Ue / Ie: 24 V / 6 A, 125 V / 1.1 A, 250 V / 0.4 A, EN 60947-5-1
    • Usage category at AC 15Ue / Ie: 250 V / 6 A, 400 V / 4 A, 500 V / 1 A, EN 60947-5-1
    • Contact allocation1NC + 1NO
    • Contact openingForce-fit
    • Short circuit protected500 V, 10 A, type aM, IEC 60269-1
    • Contact protectionProtective insulation O
    • Performance data
      • Rated insulation voltage500 V AC, 600 V DC
      • Conventional thermal current, max.10 A